CSLB C-10 Electrical ContractorSafety and TestingHard

During an arc flash risk assessment, an electrical contractor determines that the incident energy at a specific piece of equipment is 9 cal/cm². According to NFPA 70E, what is the minimum Arc Flash PPE Category (Hazard/Risk Category) required for work on this equipment, assuming the hazard cannot be eliminated?

  1. ACategory 1
  2. BCategory 3
  3. CCategory 2
  4. DCategory 4
Show answer & explanation

Correct answer: B. Category 3

NFPA 70E Table 130.7(C)(15)(b) or similar tables (depending on edition) specifies PPE categories based on incident energy. An incident energy of 9 cal/cm² falls into Arc Flash PPE Category 3, which requires a minimum of 25 cal/cm² arc-rated clothing.

Why the other options are wrong

  • A. Category 1 is for 1.2 to <4 cal/cm².
  • C. Category 2 is for 4 to <8 cal/cm².
  • D. Category 4 is for 25 to <40 cal/cm².

Arc Flash PPE Categories

A classification system by NFPA 70E that specifies the minimum arc rating of PPE required based on calculated incident energy levels.

  • Higher category = higher arc rating
  • Determined by incident energy calculations
  • Ensures worker protection from arc flash

Memory trick: PPE Categories: 1.2, 4, 8, 25!

More Safety and Testing questions