Journeyman Electrician Exam (NEC)Equipment and DevicesHard

A technician is installing a single-phase, 120-volt, 15-ampere hermetic refrigerant motor-compressor. What is the maximum rating of the branch-circuit overcurrent protective device (OCPD) permitted if the motor-compressor's rated-load current (RLC) is 12 amperes?

  1. A20 amperes
  2. B25 amperes
  3. C15 amperes
  4. D30 amperes
Show answer & explanation

Correct answer: A. 20 amperes

According to NEC 440.22(A), the branch-circuit short-circuit and ground-fault protective device for a hermetic refrigerant motor-compressor shall be capable of carrying the starting current of the motor-compressor and not exceed 175% of the motor-compressor rated-load current (RLC). So, 12 A * 1.75 = 21 A. If the protective device selected is not sufficient for the starting current, it can be increased, but shall not exceed 225% of the RLC. However, 21A is not a standard size, so the next higher standard size, 20A, is allowed as it is below 225% (12A * 2.25 = 27A).

Why the other options are wrong

  • B. This exceeds 175% of the RLC (21A) and is not the next standard size.
  • C. This is below the calculated maximum of 21A (175% of 12A).
  • D. This exceeds 225% of the RLC (27A) and is not permitted under normal circumstances.

Hermetic Motor-Compressor OCPD Sizing

The branch-circuit short-circuit and ground-fault protective device for a hermetic refrigerant motor-compressor must be sized between 175% and 225% of the motor-compressor's rated-load current (RLC), with the lower value (175%) being the starting point, rounded to the next standard size.

  • NEC 440.22(A) governs this sizing.
  • Initial sizing is 175% of RLC.
  • Can be increased up to 225% of RLC if needed for starting current.
  • Must use standard OCPD sizes (NEC 240.6).

Memory trick: Cool compressor needs its own special protection math: 175 to 225.