A three-phase motor operates on a 480V supply and draws 30 amps. If the motor has a power factor of 0.85, what is the approximate reactive power consumed by the motor?

  1. A29.8 kVAR
  2. B24.9 kVAR
  3. C22.3 kVAR
  4. D14.4 kVAR
Show answer & explanation

Correct answer: D. 14.4 kVAR

Reactive power (Q) in a three-phase system is calculated using the formula Q = √3 * V * I * sin(θ). First, find the angle θ using the power factor (cos(θ) = 0.85), then calculate sin(θ) and apply the formula.

Why the other options are wrong

  • A. This value is too high, indicating a misapplication of the power formula components.
  • B. This is likely a calculation error, possibly confusing real or apparent power.
  • C. This might be a miscalculation of the power factor angle or an incorrect formula.

Three-Phase Reactive Power

Reactive power in a three-phase system is the portion of apparent power that does not perform useful work; it is measured in volt-amperes reactive (VAR).

  • Calculated as Q = √3 * V * I * sin(θ).
  • Power factor (PF) = cos(θ).
  • Represents energy stored and returned to the source.

Memory trick: Power Triangle: Real is horizontal, Reactive is vertical, Apparent is the hypotenuse.