A technician is working on a centrifugal chiller that uses R-123. Due to the very low operating pressure, which of the following is the most significant concern when operating this type of system?

  1. AHigh discharge pressure causing compressor overload.
  2. BRefrigerant migration to the compressor oil.
  3. CAir and moisture infiltration into the system.
  4. DExcessive superheat leading to poor cooling.
Show answer & explanation

Correct answer: C. Air and moisture infiltration into the system.

Centrifugal chillers using very low-pressure refrigerants like R-123 operate below atmospheric pressure on the low side. This creates a constant risk of air and moisture being drawn into the system through leaks, which are non-condensable and can severely impair efficiency and lead to acid formation.

Why the other options are wrong

  • A. High discharge pressure is a concern for most systems, but not specific to 'very low operating pressure' systems, which primarily face suction side issues.
  • B. Refrigerant migration is a general concern, but not the *most significant* for very low-pressure systems compared to air/moisture infiltration.
  • D. Excessive superheat is a symptom of various issues, but air/moisture infiltration is a more fundamental problem for these systems.

Low-Pressure Chiller Concerns

Centrifugal chillers using very low-pressure refrigerants operate below atmospheric pressure on the low side. The most significant concern for these systems is the infiltration of air and moisture through leaks, as these are non-condensable contaminants that degrade performance and can cause system damage.

  • Operate below atmospheric pressure.
  • Leaks draw in air/moisture.
  • Non-condensables reduce efficiency.
  • Moisture leads to acid formation.

Memory trick: Below zero, air and water flow.