Commercial Building Inspector B2Roof Ceiling ConstructionMedium

A contractor is installing a new roof covering on a Type II-A commercial building. The roof deck consists of structural concrete. The chosen roof covering is a modified bitumen membrane system. According to IBC, what is the minimum required Class fire classification for this roof covering assembly?

  1. AClass B
  2. BClass A
  3. CClass C
  4. DNo classification required
Show answer & explanation

Correct answer: B. Class A

For Type I or II construction, which includes Type II-A, the IBC generally requires a Class A roof covering assembly. Structural concrete decks often contribute to a higher assembly rating, but the roof covering itself must meet the Class A requirement.

Why the other options are wrong

  • A. Class B is for less fire-resistive construction types or specific conditions, not typically Type II-A.
  • C. Class C is the lowest classification and is generally not permitted for commercial buildings of Type II-A construction.
  • D. A fire classification is almost always required for roof coverings on commercial buildings, especially Type II-A.

Roof Covering Fire Classification (Type II-A)

The minimum fire classification required for roof coverings on Type II-A commercial buildings, which is Class A, indicating high fire resistance.

  • Class A is highest rating.
  • Required for Type I & II construction.
  • Prevents flame propagation.

Memory trick: Building Type II-A, Class A roof must play, keeping fire away.