CSLB C-10 Electrical ContractorPlanning and EstimatingMedium

A residential client is planning a new laundry room. The plans specify a 120V, 20A branch circuit for the washing machine and a separate 120V, 20A branch circuit for the gas dryer receptacle. What is the minimum load (in VA) that must be calculated for the laundry branch circuit, according to NEC 220.52(B)?

  1. A1500 VA
  2. B1000 VA
  3. C2400 VA
  4. D2000 VA
Show answer & explanation

Correct answer: A. 1500 VA

According to NEC 220.52(B), for dwelling units, a minimum load of 1500 VA must be included for each 20A laundry branch circuit.

Why the other options are wrong

  • B. 1000 VA is too low for a dedicated laundry branch circuit calculation.
  • C. 2400 VA represents the full capacity of a 20A, 120V circuit (20A * 120V), not the minimum required load for calculation.
  • D. 2000 VA is not the specified minimum for a laundry branch circuit.

Laundry Branch Circuit Load

A specific minimum VA load mandated by the NEC for each dedicated laundry branch circuit in dwelling units, ensuring adequate capacity for laundry appliances.

  • NEC 210.11(C)(2) requires at least one 20A branch circuit for the laundry area.
  • NEC 220.52(B) specifies a minimum calculated load of 1500 VA for this circuit.
  • This load is applied even if the actual washing machine draws less, or if a gas dryer is used (which still requires a 120V receptacle for its motor/controls).

Memory trick: Laundry load: 'One' circuit, 'Fixed' VA 'Minimum'.

More Planning and Estimating questions