A newly installed motor in a commercial facility draws 50A at 480V, 3-phase. The motor nameplate indicates a power factor of 0.85. What is the approximate apparent power (S) consumed by this motor?

  1. A20.4 kVA
  2. B24.0 kVA
  3. C41.6 kVA
  4. D35.4 kVA
Show answer & explanation

Correct answer: C. 41.6 kVA

For a 3-phase circuit, apparent power (S) is calculated as S = (√3 * V * I) / 1000 for kVA. S = (1.732 * 480V * 50A) / 1000 = 41.568 kVA, which approximates to 41.6 kVA. The power factor is used for calculating real power, not apparent power directly from V and I.

Why the other options are wrong

  • A. Incorrect. This value might be obtained by multiplying V*I*PF (real power) and then dividing by 1.732.
  • B. Incorrect. This value might be obtained from a miscalculation or incorrect formula application.
  • D. Incorrect. This value represents the real power (P = √3 * V * I * PF = 41.568 kVA * 0.85 = 35.33 kVA).

Apparent Power in 3-Phase Systems

Apparent power (S) is the total power flowing in an AC circuit, measured in Volt-Amperes (VA), and includes both real and reactive power. For a 3-phase system, it's calculated using the line-to-line voltage and line current.

  • S = √3 * V_line * I_line
  • Units are Volt-Amperes (VA) or kiloVolt-Amperes (kVA)
  • Power factor is not directly used in this calculation but relates apparent to real power.

Memory trick: SARAH: S is Apparent, R is Real, H is Hypotenuse of VAR triangle.