Master Electrician Exam (NEC)General Electrical KnowledgeEasy

A master electrician is planning the installation of a new 480V, 3-phase motor with a full-load current (FLA) of 60A. According to NEC Article 430, what is the minimum continuous current rating required for the branch-circuit conductors supplying this motor if it is not a hermetic refrigerant motor?

  1. A75A
  2. B90A
  3. C125A
  4. D60A
Show answer & explanation

Correct answer: A. 75A

For other than hermetic refrigerant motors, branch-circuit conductors supplying a single motor must have an ampacity not less than 125% of the motor's full-load current rating, as per NEC 430.22(A). Therefore, 60A * 1.25 = 75A.

Why the other options are wrong

  • B. This value would be 150% of the FLA, which is typically for overcurrent protection, not conductor sizing.
  • C. This value would be 208% of the FLA, which is significantly higher than the NEC requirement for conductors.
  • D. This is the motor's full-load current (FLA), but NEC requires an overcurrent factor for conductors.

Motor Branch-Circuit Conductor Sizing

NEC requires motor branch-circuit conductors to be sized at a minimum percentage of the motor's full-load current to safely carry continuous operating currents and accommodate starting currents.

  • For non-hermetic motors, conductors must be sized at 125% of the motor FLA.
  • This factor accounts for continuous operation and motor starting currents.
  • Refer to NEC Article 430 for specific requirements.

Memory trick: Motor Conductors Need Extra Amps for Smooth Starts.