Commercial Building Inspector B2Floor ConstructionMedium

A commercial building inspector is examining the installation of a new concrete floor slab on grade in a warehouse. The plans specify a vapor retarder directly beneath the slab. According to the IBC, what is the minimum perm rating required for this vapor retarder?

  1. A1.0 perm
  2. B0.01 perm
  3. C0.3 perm
  4. D0.1 perm
Show answer & explanation

Correct answer: B. 0.01 perm

The IBC, referencing ASTM E1745, requires a vapor retarder beneath concrete slabs on grade to have a maximum permeance of 0.01 perm (Class A) when tested in accordance with ASTM E96.

Why the other options are wrong

  • A. 1.0 perm is typically considered a vapor retarder but not a vapor barrier for critical applications like under slabs.
  • C. 0.3 perm is too high for a vapor retarder required beneath a concrete slab on grade.
  • D. 0.1 perm is a common requirement for vapor barriers in some wall assemblies, but not sufficiently low for beneath concrete slabs.

Slab-on-Grade Vapor Retarder

A vapor retarder beneath a concrete slab on grade is essential to prevent moisture migration from the ground into the building, protecting floor finishes and indoor air quality.

  • Required by IBC for slabs on grade.
  • Minimum Class A material per ASTM E1745.
  • Maximum permeance of 0.01 perm.
  • Installed directly under the slab.

Memory trick: Moisture's foe, a perm so low, under the slab, where roots don't grow.