Commercial Building Inspector B2Floor ConstructionEasy

An inspector is evaluating the installation of a new wood floor system in a commercial building. The plans specify the use of fire-retardant-treated wood (FRTW) for the floor joists. Which of the following conditions is NOT permitted for the use of FRTW in floor construction according to the IBC?

  1. AIn roof construction where the FRTW is exposed to the weather.
  2. BIn areas where the relative humidity will not exceed 95%.
  3. CIn concealed spaces where the temperature will not exceed 150°F (66°C).
  4. DWithin 6 inches (152 mm) of the ground, exposed to weather.
Show answer & explanation

Correct answer: D. Within 6 inches (152 mm) of the ground, exposed to weather.

The IBC specifically prohibits the use of fire-retardant-treated wood where it is exposed to the weather, within 6 inches (152 mm) of the ground, or in interior applications where the relative humidity will be greater than 95%.

Why the other options are wrong

  • A. FRTW is permitted in roof construction where it is NOT exposed to weather, but this option states it IS exposed, making it also a prohibited condition, however, the question asks for NOT permitted for floor construction, making C the most direct answer.
  • B. FRTW is permitted where relative humidity will not exceed 95% for interior applications.
  • C. FRTW is permitted in concealed spaces where the temperature will not exceed 150°F (66°C).

FRTW Limitations

Fire-retardant-treated wood has specific limitations on its use, primarily concerning exposure to moisture and high temperatures, to ensure its effectiveness.

  • Not permitted where exposed to weather.
  • Not permitted within 6 inches of the ground.
  • Not permitted in interior applications with relative humidity > 95%.
  • Permitted in concealed spaces up to 150°F (66°C).

Memory trick: FRTW fears the wet, the ground, and sun's direct fret.