Master Electrician Exam (NEC)Special Occupancies, Equipment, and ConditionsMedium

A master electrician is installing a new general-purpose receptacle for maintenance equipment within 20 feet of a permanently installed swimming pool. The receptacle is located 7 feet horizontally from the inside wall of the pool. Which of the following statements is true regarding its installation?

  1. AThe receptacle must be a locking-type receptacle.
  2. BThe receptacle must be GFCI protected.
  3. CThe receptacle does not require GFCI protection if it is not readily accessible.
  4. DThe receptacle is permitted to be located within 6 feet of the pool if it has a weather-resistant enclosure.
Show answer & explanation

Correct answer: B. The receptacle must be GFCI protected.

NEC 680.22(A)(5) requires all 125-volt, single-phase, 15- and 20-ampere receptacles located within 20 feet of the inside wall of a swimming pool to have ground-fault circuit-interrupter (GFCI) protection. The 7-foot distance is within this 20-foot zone.

Why the other options are wrong

  • A. Locking-type receptacles are not a general requirement for all receptacles near pools; GFCI protection is the primary concern.
  • C. Accessibility does not negate the GFCI requirement for receptacles near pools.
  • D. Receptacles are generally not permitted within 6 feet of the pool, even with weather-resistant enclosures, unless specific conditions are met for permanent pool motors or lighting, which is not the case here.

Swimming Pool Area Receptacle GFCI

Requirement for ground-fault circuit-interrupter protection for all 125-volt, 15- and 20-ampere receptacles located within 20 feet of a swimming pool.

  • Applies to 125V, 15A/20A receptacles.
  • Distance is within 20 feet of pool's inside wall.
  • Mandated by NEC 680.22(A)(5).

Memory trick: Near a pool, every outlet within 20 feet needs a GFCI like a lifeguard.

More Special Occupancies, Equipment, and Conditions questions