Master Electrician Exam (NEC)Special Occupancies, Equipment, and ConditionsHard

A master electrician is installing a new wind electric system for a commercial property. The system includes an inverter that is connected to the normal power supply. The inverter has a continuous output current of 50 amperes. What is the minimum continuous current rating required for the conductors connecting the inverter output to the building's electrical system?

  1. A80 amperes
  2. B75 amperes
  3. C62.5 amperes
  4. D50 amperes
Show answer & explanation

Correct answer: C. 62.5 amperes

According to NEC 694.30(A) and 210.20(A), conductors supplying continuous loads (which inverter output is considered) must have an ampacity not less than 125% of the continuous current rating of the load. Therefore, for a 50-ampere continuous output, the conductors must be rated for at least 50 A * 1.25 = 62.5 A.

Why the other options are wrong

  • A. This is significantly higher than the minimum required.
  • B. This is higher than the minimum required, but 62.5A is the minimum.
  • D. This is the continuous output current, but conductors for continuous loads require a 125% factor.

Wind System Inverter Conductor Sizing

Sizing conductors for the continuous output of a wind electric system inverter, treating it as a continuous load.

  • Inverter output is a continuous load.
  • Conductor ampacity must be 125% of continuous current.
  • Governed by NEC 694.30(A) and 210.20(A).

Memory trick: Wind inverter conductors need 25% extra capacity, like a strong breeze needs extra sail.