Master Electrician Exam (NEC)Special Occupancies, Equipment, and ConditionsMedium

A master electrician is installing a new data processing system in a commercial office building. The system requires a dedicated branch circuit. According to NEC, what is the minimum size of the grounding conductor for a 20-ampere branch circuit supplying data processing equipment, if the circuit conductors are No. 12 AWG copper?

  1. ANo. 14 AWG copper
  2. BNo. 10 AWG copper
  3. CNo. 12 AWG copper
  4. DNo. 8 AWG copper
Show answer & explanation

Correct answer: C. No. 12 AWG copper

NEC Table 250.122 specifies the minimum size of equipment grounding conductors. For a 20-ampere overcurrent protective device, the minimum size for a copper equipment grounding conductor is No. 12 AWG. This applies generally and also to data processing systems unless specific conditions require larger sizes.

Why the other options are wrong

  • A. No. 14 AWG copper is typically for 15-ampere circuits, not adequate for a 20-ampere circuit.
  • B. No. 10 AWG copper is larger than the minimum required for a 20-ampere circuit, typically used for 60-ampere OCPD.
  • D. No. 8 AWG copper is significantly larger than necessary for a 20-ampere circuit, typically used for 100-ampere OCPD.

Data Processing EGC Sizing

The minimum size of the equipment grounding conductor for dedicated branch circuits supplying data processing equipment, determined by the circuit's overcurrent protective device rating.

  • Follows general EGC sizing rules (NEC 250.122).
  • Critical for sensitive electronic equipment.
  • Ensures proper fault current path.

Memory trick: Circuit's OCPD sets the EGC's pace, Table 250.122, no guessing case!