EPA Section 608 Universal Certification ExamType II (High-Pressure Appliances)Medium

A technician is performing a major repair on a high-pressure appliance containing R-410A. The system has a charge of 30 pounds. After recovery, what is the required evacuation level before recharging the system?

  1. A0 psig
  2. B10 inches Hg vacuum
  3. C15 inches Hg vacuum
  4. D25 inches Hg vacuum
Show answer & explanation

Correct answer: C. 15 inches Hg vacuum

For high-pressure appliances with a charge of more than 10 pounds, after a major repair, the EPA requires evacuation to 15 inches of mercury vacuum. This ensures thorough removal of non-condensables and moisture.

Why the other options are wrong

  • A. 0 psig is atmospheric pressure, not a vacuum level.
  • B. 10 inches Hg vacuum is required for high-pressure appliances with 10 pounds or less of refrigerant after a major repair.
  • D. 25 inches Hg vacuum is not a standard EPA evacuation level for this specific scenario.

High-Pressure Appliance Evacuation Levels (Major Repair, >10 lbs)

EPA regulations mandate specific vacuum levels for high-pressure appliances after recovery, depending on the refrigerant charge size and type of repair.

  • For major repairs on appliances with >10 lbs, 15 inches Hg vacuum is required.
  • For major repairs on appliances with <=10 lbs, 10 inches Hg vacuum is required.
  • These levels prevent contamination and ensure proper system operation.

Memory trick: Major fix, greater charge, deeper vacuum to discharge!

More Type II (High-Pressure Appliances) questions