EPA Section 608 Universal Certification ExamType II (High-Pressure Appliances)Medium

After a major repair on a high-pressure appliance, a technician must evacuate the system to a certain level. If the system holds 35 pounds of R-407C and the repair is not followed by disposal, what is the required evacuation level?

  1. A15 inches Hg vacuum
  2. B0 psig
  3. C10 inches Hg vacuum
  4. D25 inches Hg vacuum
Show answer & explanation

Correct answer: C. 10 inches Hg vacuum

For high-pressure appliances with a charge of less than 200 pounds of refrigerant, when the appliance is not being disposed of, the required evacuation level is 10 inches Hg vacuum. R-407C is a high-pressure refrigerant.

Why the other options are wrong

  • A. 15 inches Hg vacuum is for very high-pressure appliances or high-pressure appliances manufactured before 1993 with 200+ lbs of refrigerant.
  • B. 0 psig is for very high-pressure appliances or small high-pressure appliances being disposed of with self-contained recovery.
  • D. 25 inches Hg vacuum is for low-pressure appliances.

High-Pressure Appliance Evacuation Levels (Major Repair, Not Disposal)

EPA regulations define specific evacuation levels for high-pressure appliances after major repairs but before recharging, depending on the refrigerant charge size and whether the appliance is being disposed of.

  • For high-pressure appliances with <200 lbs of refrigerant, 10 inches Hg vacuum is required when not being disposed of.
  • This ensures non-condensables and residual refrigerant are removed.
  • Different standards apply for disposal or larger systems.

Memory trick: Post-repair, not disposal, ten inches is the call, for small charges, stand tall.