Commercial Building Inspector B2Public Safety and Special ConstructionEasy

A building inspector is reviewing the plans for a new four-story multi-tenant commercial building (Group B). The building is equipped with an automatic sprinkler system throughout. What is the minimum required fire-resistance rating for the exit access corridors in this building?

  1. A0 hours
  2. B1 hour
  3. C2 hours
  4. D1.5 hours
Show answer & explanation

Correct answer: A. 0 hours

According to IBC Table 1020.1, Group B occupancies with an automatic sprinkler system throughout are permitted to have exit access corridors with no fire-resistance rating.

Why the other options are wrong

  • B. This rating is typically required for unsprinklered Group B buildings or certain other occupancies.
  • C. This rating is typically for fire walls or shafts, not standard exit access corridors.
  • D. This rating is not a standard corridor rating in the IBC for this occupancy type.

Corridor Fire Rating (Sprinklered B Occupancy)

In Group B occupancies equipped with an automatic sprinkler system throughout, exit access corridors are not required to have a fire-resistance rating.

  • Applies to Group B occupancies.
  • Requires full automatic sprinkler system.
  • Referenced in IBC Table 1020.1.

Memory trick: Corridor's fire shield depends on the building's sprinkler 'B'est practice.