A technician is sizing a UPS for a rack containing three identical servers, each drawing 400W under normal load. The UPS operates the connected load at a power factor of 0.9. Which of the following standard UPS VA ratings should the technician select to safely support this load?

  1. A1000VA
  2. B1500VA
  3. C2000VA
  4. D1200VA
Show answer & explanation

Correct answer: B. 1500VA

Total wattage is 3 x 400W = 1200W. VA = Watts / Power Factor = 1200 / 0.9 = 1333.3VA. The smallest standard UPS rating that exceeds this requirement is 1500VA; a 1200VA unit would be undersized.

Why the other options are wrong

  • A. Far below the calculated requirement of about 1333VA.
  • C. Oversized; unnecessarily exceeds the requirement and increases cost.
  • D. Equal to the wattage but below the required VA after dividing by the power factor.

UPS VA Sizing

UPS capacity is rated in VA (volt-amps); actual wattage divided by the power factor gives the required VA rating needed to support a load.

  • VA = Watts / Power Factor
  • Power factor for IT loads is often around 0.9
  • Always round up to the next standard UPS VA rating

Memory trick: Divide watts by the power factor to reveal the true VA giant hiding underneath.