CSLB General Building (B)Site Work, Foundations and ConcreteMedium

A contractor is placing a 4-inch-thick interior concrete slab-on-grade and must determine control joint spacing to minimize random shrinkage cracking. Using the standard industry rule of thumb, what is the maximum recommended joint spacing?

  1. A16 to 20 feet
  2. B24 to 30 feet
  3. C8 to 12 feet
  4. D4 to 6 feet
Show answer & explanation

Correct answer: C. 8 to 12 feet

The common industry rule of thumb is that control joint spacing in feet should be about 2 to 3 times the slab thickness in inches. For a 4-inch slab, this gives a spacing of 8 to 12 feet (4 x 2 = 8, 4 x 3 = 12).

Why the other options are wrong

  • A. This spacing is too wide and increases risk of uncontrolled cracking.
  • B. This far exceeds recommended spacing for a 4-inch slab.
  • D. This spacing is too tight and would be unnecessarily costly.

Control Joint Spacing

Joints cut or formed into a concrete slab at regular intervals to control the location of shrinkage cracks.

  • Rule of thumb: spacing (ft) = 2 to 3 times slab thickness (in)
  • Joints should be cut within 6-12 hours of finishing for best crack control
  • Panel aspect ratio should not exceed about 1.5:1

Memory trick: Thickness times two or three tells you where the joint should be.