CSLB General Building (B)Mechanical, Electrical, Plumbing CoordinationEasy

A contractor is selecting fire blocking material for concealed stud cavities in a wood-framed home. Which of the following meets the California Residential Code minimum requirement for solid lumber fire blocking?

  1. A1/4-inch plywood with taped joints
  2. BNominal 2-inch lumber installed as a single thickness
  3. CNominal 1-inch lumber installed as a single thickness
  4. DNominal 1-inch lumber with joints aligned (not staggered)
Show answer & explanation

Correct answer: B. Nominal 2-inch lumber installed as a single thickness

CRC R602.8 allows nominal 2-inch (actual 1-1/2 inch) lumber as a single-thickness fire blocking material. Single 1-inch boards are too thin unless doubled with staggered (broken lap) joints, and thin plywood without backing does not qualify.

Why the other options are wrong

  • A. 1/4-inch plywood is too thin and not an approved fire blocking material.
  • C. A single 1-inch board alone is insufficient thickness for fire blocking.
  • D. Two 1-inch boards must have staggered (broken lap) joints, not aligned joints, to qualify.

Fire Blocking Material Thickness

CRC R602.8 lists approved fire blocking materials, including nominal 2-inch lumber, two 1-inch boards with staggered joints, or approved panel products with backed joints.

  • Nominal 2-inch lumber (actual 1.5") qualifies as single-thickness fire block.
  • Two 1-inch boards need staggered/broken lap joints.
  • Gypsum board, mineral wool, and certain panel products are also approved.

Memory trick: 'Two-by lumber blocks the fire, thin boards alone will only conspire (to fail).'