CSLB C-39 Roofing ContractorFlashing, Ventilation and InsulationHard

A vaulted cathedral ceiling assembly (no attic space) covers 3,600 square feet and will use the 1/150 ratio with vents split equally between the eave and ridge. How many square inches of net free area must be provided at the EAVE intake side?

  1. A1,728 square inches
  2. B864 square inches
  3. C1,152 square inches
  4. D3,456 square inches
Show answer & explanation

Correct answer: A. 1,728 square inches

Total vent area = 3,600 ÷ 150 = 24 sq ft = 3,456 sq in. Split 50/50 between eave and ridge, the eave (intake) portion is 3,456 ÷ 2 = 1,728 sq in.

Why the other options are wrong

  • B. This is only a quarter of the total requirement.
  • C. This equals the exhaust-only value under a 1/300 ratio, not this scenario.
  • D. This is the full total, not just the intake half.

Cathedral Ceiling Ventilation Math

Vaulted ceilings without attic space follow the same net free area math as attics, using 1/150 or 1/300 ratios and typically requiring balanced airflow channels.

  • Total sq ft = ceiling area ÷ ratio denominator.
  • Multiply by 144 to convert to sq in.
  • Balanced systems split the total evenly between intake and exhaust.

Memory trick: '150 rule, then split the tool.'