CSLB C-39 Roofing ContractorFlashing, Ventilation and InsulationMedium

A single-story home has an attic floor area of 2,400 square feet. The attic will be vented using the 1/300 ratio with a balanced system (50% intake at the eaves, 50% exhaust at the ridge). How many square inches of net free ventilation area are required at the ridge (exhaust side) alone?

  1. A576 square inches
  2. B2,304 square inches
  3. C288 square inches
  4. D1,152 square inches
Show answer & explanation

Correct answer: A. 576 square inches

Total required vent area = 2,400 ÷ 300 = 8 sq ft = 1,152 sq in. With a balanced 50/50 split, the ridge (exhaust) portion is 1,152 ÷ 2 = 576 sq in.

Why the other options are wrong

  • B. This doubles the actual total requirement in error.
  • C. This is only a quarter of the total required area.
  • D. This is the full total, not just the exhaust half.

1/300 Balanced Ventilation Ratio

When a vapor retarder is present, attics may use 1 sq ft of net free vent area per 300 sq ft of attic floor area, split evenly between intake and exhaust.

  • Formula: Attic area ÷ 300 = total sq ft of vent area.
  • Convert to sq in by multiplying by 144.
  • Balanced systems split total evenly: 50% low, 50% high.

Memory trick: 'Divide by 300, then split it in two.'